Free cheat sheets and quick-math calculators for HVACR techs. Bookmark this page and use it on the job.

Free Cheat Sheets

One-page field guides. Free to download, print and keep in the truck.

Compressor Diagnosis Checklist

Prove it failed before you change it, then find what killed it.

Download PDF

A2L Refrigerant Quick Guide

R-454B and R-32: cylinders, tools and staying safe on the job.

Download PDF

Startup Checklist: No Callbacks

Every check before you drive away, with a readings record.

Download PDF

Duct Sizing Quick Guide

The steps, a worked example, velocity limits and layout rules.

Download PDF

Field Calculators

Target Superheat (Piston Systems)

For fixed-orifice (piston) systems only. TXV and EEV systems are charged by subcooling.

Formula: (3 × indoor WB − 80 − outdoor DB) ÷ 2. Always follow the manufacturer’s charging chart when one is provided.

Superheat & Subcooling

Enter the saturation temperatures from your gauges and your line temperatures.

Line-Set Charge Adjustment

How much refrigerant to add or remove for line-set length.

0.6 oz/ft is common for a 3/8″ liquid line. Use the oz/ft from the unit’s installation manual.

Duct Velocity

Limits are residential guidelines from ACCA Manual D.

Airflow from Temperature Rise

Estimate furnace airflow from output and measured temperature rise.

Formula: CFM = BTU/h output ÷ (1.08 × temperature rise). Use output, not input. Check the rise against the furnace nameplate range.

Total External Static Pressure

Add the two readings and ignore the signs. Supply: after the coil, before the first fitting. Return: between the filter and the blower.

These tools are for training and quick field estimates. Always follow the equipment manufacturer’s instructions, local codes and ACCA procedures. Want to learn the why behind the math? See the on-demand training at gilliscoach.com.